Compare\AgentStation.ini file
Common
In the [Common] section, the following keys can be configured:
| Key | Description | Values | Default value |
|---|---|---|---|
| 4930 | Specifies the maximum number of comparisons that can run simultaneously across all compare classes. This key can also be set in the corresponding section of the respective compare type to apply a stricter limit for that specific type. This type-specific value must be less than or equal to the value under [Common] and must never exceed it. | 1 ... 1024 | 5 |
| 4932 | Specifies what to do with files that are relevant for a comparison (Archive.zip and Backup.zip) after a comparison has been completed. | 0: The Archive.zip and Backup.zip files are not deleted and may be used for further comparisons. 1: The Backup.zip file is deleted. | 1 |
ABBFreelance
In the [ABBFreelance] section, the following key can be configured:
| Key | Description | Values | Default value |
|---|---|---|---|
| 7335 | Specifies the full path to the ABB Freelance installation directory. | Path | Path to the application of the registered COM server CBF.Application |
CODESYS
In the [CODESYS] section, the following key can be configured:
| Key | Description | Values | Default value |
|---|---|---|---|
| Editors | Specifies the path of the CODESYS editor for Codesys 3. | {Absolute path of the editor EXE file}?{Codesys profile used to open the projects}. | No path |
FactoryTalkView
In the [FactoryTalkView] section, the following key can be configured:
| Key | Description | Values | Default value |
|---|---|---|---|
| 7030 | Specifies the MS SQL Server instance. The instance must match the database version of the FactoryTalk View project. | Name of the instance | FTVIEWX64TAGDB |
Lenze840DProtec
In the [Lenze840DProtec] section, the following key can be configured:
| Key | Description | Values | Default value |
|---|---|---|---|
| 7350 | Specifies the full path to the installation directory of the L-Force Engineer editor. | Path | No path |
RSLogix5000
In the [RSLogix5000] section, the following key can be configured:
| Key | Description | Values | Default value |
|---|---|---|---|
| 7111 | Specifies whether Know-How protection is enabled or whether the contents of all blocks should be displayed. Know-How Protection: Certain add-on instructions and routines are configured using external tools so that the content is not displayed. With the value N, this content is still used for comparison and displayed. | Y/N | Y |
SchneiderModsoft
In the [SchneiderModsoft] section, the following key can be configured:
| Key | Description | Values | Default value |
|---|---|---|---|
| 7321 | Specifies the storage location for external macros. | Complete path to installation directory for Schneider Modsoft | No path |
SimaticS7
In the [SimaticS7] section, the following key can be configured:
| Key | Description | Values | Default value |
|---|---|---|---|
| 7178 | Specifies whether the Know-How protection is enabled or the contents of the blocks should be displayed. Know-How Protection: Certain blocks are configured using external tools so that the content is not displayed. With the value N, this content is still used for comparison and displayed. | Y/N | Y |
WonderwareSystemPlatform
In the [WonderwareSystemPlatform] section, the following key can be configured:
| Key | Description | Values | Default value |
|---|---|---|---|
| 40300 | Specifies the MS SQL server instance. If there is a key present in the INI file, this value will be used instead of those entered in component configuration. | Name of the instance | Empty string |
WinCC
In the [WinCC] section, the following keys can be configured:
| Key | Description | Values | Default value |
|---|---|---|---|
| 7030 | Specifies the MS SQL Server instance. | Name of the instance | WinCC |
| 7031 | Specifies whether the WinCC ES application should be used for comparison. When selected, image elements are compared in detail and CScript differences are shown in plain text. | Y/N | N |
WinCCFlexible
In the [WinCCFlexible] section, the following key can be configured:
| Key | Description | Values | Default value |
|---|---|---|---|
| 7050 | Specifies the MS SQL server instance. The instance must match the database version of the WinCCflexible project. | Name of the instance | WINCCFLEXEXPRESS |