In the [{Upload type}] section, the following key can be configurated:

Key Description Values Default value
9850 Specifies the time period after which the execution of the jobs of the corresponding upload class is canceled.
The timeout specified here overwrites the global timeout for this upload class.
<10 ... 540> 30

Section GEProficyMachineEdition

In the [GEProficyMachineEdition] section, the following key can be configurated:

Key Description Values Default value
36871 Issues a warning if forced variables are used in a controller.
The warning only shows in which controller the forced variable is used and not which variable it is.
Y/N N

Section RSLogix_CLX

In the [RSLogix_CLX] section, the following keys can be configurated:

Key Description Values Default value
5150 Specifies whether the RSLogix 5000 development system should be used for the upload. Y/N Y
5151 Specifies whether the communication path should be set automatically via remote control by PAExec. Y/N Y

Section SimaticS7

In the [SimaticS7] section, the following keys can be configurated:

Key Description Values Default value
5009 Specifies which versions of the SIMATIC S7 Manager are enabled. If an offline S7 project is used as the target of an upload, the released versions of the editor with which this offline S7 project was last edited for writing are stored here. {Versions separated by a comma} 5.1,5.2,5.3,5.4,5.5,5.6
5097 Specifies whether all S7 project data or only the files relating to the respective S7 program should be included in the backup. Y/N Y

Section Sinumerik840D

In the [Sinumerik840D] section, the following keys can be configurated:

Key Description Values Default value
5191 Specifies the number of connection attempts. 0 ... 100 10