Configuring BECKHOFF TwinCAT V3 jobs

For a job, you can also use the Upload boot project option in the job settings to save the boot project and compare it with the data from the runtime. This allows you to check whether the runtime that is executed on the IPC was created from the boot project in the memory (see step 7). If the Project Sources checkbox is activated in the TwinCAT subprojects (in TwinCat XAE), the runtimes are saved in the Backup with (uploading is carried out via the Enable configuration function).

For information on the requirements for creating a job, see Configuring octoplant.

Info

The backup can only be edited if you have also copied all Project Sources to the controller.

Procedure

Upload fails with Secure ADS enabled

Upload is not possible if the connection is encrypted.

Disable Secure ADS to proceed.

Figure: Encryption settings

  1. Create a job with the TwinCAT upload type.

  2. If the component contains several projects, select the desired project from the dropdown menu under TwinCAT settings.

  3. Activate the Upload boot project option to include the boot project in the upload.
  4. In the Device field, enter the IP address or the name of the IPC.
  5. In the AMS Net ID field, enter the AMS Net ID of the IPC.
  6. Available runtimes are listed under Runtime system. Select the one you want to use.

    Info

    If you select <All> as the runtime system, the backup is recoverable.

  7. If necessary, adjust the Sleep Interval Between Data Packets value under Advanced to either increase or decrease the delay.